Turbo Core Compressor Problems
The screen shot shows a compressor on a new turbo core chiller which we remotely monitor. This chiller had just been serviced with the chiller being powered off and back on at the point indicated 1.38. After which the compressor pcbs failed, we noticed this and alerted the installing contractor who then attended site to correct the problem. Had we not diagnosed this fault it is possible that the compressor would have stopped and started a significant amount of times. To summarise the compressor after service went into a fault that started and stopped the compressor multiple times. The timescale shown after the 1.38 is only 40 minutes, therefore the compressors started and stopped 10 times in 40 minutes.